Psychrometrics: sensible heat factor for cooling and dehumidification For a process over a cooling coil, with h1 = enthalpy of entering air, h2 = enthalpy of leaving air, and hA = enthalpy at the end of dehumidification (apparatus dew point), choose the correct expression for the sensible heat factor (SHF).

Difficulty: Medium

Correct Answer: SHF = (h1 − hA) / (h1 − h2)

Explanation:

Given data

  • h1: enthalpy of entering air
  • h2: enthalpy of leaving air
  • hA: enthalpy at apparatus dew-point (end of dehumidification line)


Concept/Approach
For cooling and dehumidification, the sensible heat factor is the ratio of sensible heat to total heat for the 1→2 process and, in terms of psychrometric geometry, is given by the segment ratio along the process line.


Derivation (sketch-based reasoning)
Total heat removed = (h1 − h2); sensible component corresponds to (h1 − hA).
SHF = (h1 − hA) / (h1 − h2).


Sanity check
If there is no dehumidification, hA → h2 and SHF → 1, as expected for purely sensible cooling.


Final Answer
SHF = (h1 − hA) / (h1 − h2)